My AC drain gets clogged every so often. Any trips for a more permanent fix?
About 2-3 years ago the line clogged and I didn’t catch it for a while and we had some serious water damage. It just clogged again and I caught it pretty quick but it could have been bad.
Shop vac solves the immediate problem but I’d like a more permanent solution. Any ideas?
I live in Florida, I keep two things on hand for my HVAC drain line. First is condensate cleaner (less harmful to the plastic than bleach) which I use monthly and my backup is a Gallo Drain Gun. Even on my worst blockages, 2 shots of the drain gun cleared it out.
Can't say I've seen much difference, In my case, there is a place inline in the drain tube to pour in liquid so I use Algaecide in that but if you don't, use the drain pan tablets -- no idea which would work better though. It does work best as a preventative before you get buildup. My drain line is long with many twists and turns, lots of places ideal for buildup (I curse the builder for this!)
My drain has a float switch. If the line clogs and water backs up, it turns off the unit. I also have a leak sensor in the pan that integrates with my security system.
A permanent fix would be a larger drain or a backup drain.
Water sensors are a cheap investment that can be reused later. You can also buy inexpensive ones from Tuya or Aqara that are smart and should be able to notify you on your phone over just a simple one that beeps.
Do maintenance on the air filters. The water is being condensed straight from the air so it’s not hard water or anything. The only explanation is that enough dust is settling in the water that it clogs the drain. There must be some kind of air filter upstream of where dust can collect in the water line, and that air filter probably needs replacing.
The cheaper/lower quality the air filter, the less particulates it filters from the air. What dust the filter doesn't catch cycles through the system and can get caught by the AC coil. Filter effectiveness is measured by its MERV rating. The higher the rating, the more particulates it will catch.
I use a MERV 13 filter but that's because I'm alergic to the entire planet and it helps reduce airborne allergens. If you go much higher than that your furnace/air handler may struggle to blow air.
I'm assuming this is a split unit? I don't have one, but I thought there was a float protection to prevent the AC from running if there was too mich water in it. Of course, this would probably only work if the clog was near the unit itself.
"Gunk" is probably a combination of algae sludge plus any captured lint from the ventilation. Not much to do about the algae other than blast it with a disinfectant like bleach once in a while.
How's the incoming air filtration into the unit? Is it sealed reasonably well at the filter?
I have a similar issue. My line is coming from the 2nd floor and there is a pipe in the wall that drains outside newr ground level. The pipe is probably 12 foot long and takes a few bends.
I used a snake to clear the line a few weeks ago. Not entire sure what exactly is causing the clog but like you said, it's probably just gunk.
Now after I cleared the line I was ready to pull the drain out, but the pipe is like 1/2" so the snake isn't really blocking any condensate from dripping down. So for the last few weeks, I've simply left the snake in there. I'm thinking with the snake in there either maybe the gunk won't grow to clog the line so easily, or since it's already in there, all I have to do is wiggle the snake once a month and dislodge anything that might be starting to grow.
The reason I don't pull it out is because with the angle and bends in the pipe, I had a hell of a time snaking the snake up there. But once it was up there dislodged the gunk took all of 5 seconds.
The snake looks to be regular steel which will rust with water touching it, so I've ordered some stainless steel wire which I will run up the pipe ans just leave it there. It's not the beat solution but I don't have access to the source of the condensate so I have to work backwards from the drain up.