I have a 14 Amp Ryobi miter saw. In the manual it has a table for required AWG by Cord Length and Amps. For 100' and 12.1-16.0 Amps it just has a dash indicating there is no suitable AWG extension cable for this length and amp combination.
Check your line voltage at your house. There is a lot of variance in house voltage. 110-125vac.
Motors draw a minimum current and increases with load. your rating is for max load. So if you plan on a lot of deep cuts you might struggle. Smaller cuts will draw less.
Long story short 10awg should be good.
From southwire voltage calculator
Results for Minumum Conductor Size Calculation
1 conductor per phase utilizing a 10 AWG copper conductor installed Cable, Conduit (non-Steel), & Direct Burial will limit the voltage drop to 2.45% or less when supplying 14 amps for 100 feet on a 120 volt single phase system.
Nema motors are designed to work at the low range of 100v
Nema quote
An electric motor is electrically designed around the expected supply voltage with a tolerance. With NEMA (National Electrical Manufacturers Association) designs for small- and medium-voltage electric motors is +/- 10% voltage-maximum, with an allowable +/-5% frequency variation (ref.Jan 12, 2020
How much cutting are you actually going to be doing? This is going to be key. The resistance on a smaller wire (larger gage number) and longer length is going to turn the cord hot. But if you're making 3 cuts, I wouldn't worry about it. If you are going to run it 24/7, then I'd worry.
Run it for a few days at the expected use amount and keep an eye on the heat of the cord but also the outlet and plug. I do have to say that 100' is a lot. No outlets closer than that to you?